Our Low Smoke Zero Halogen cable is ideal for public areas, transport systems, factories, and any other areas where the protection of people and equipment from toxic and corrosive gases is essential. The zero halogen jacket has excellent fire and safety characteristics, giving off less smoke and emitting very low gases. This high quality solid core bulk cable is ideal for Ethernet, Fast Ethernet, Gigabit Ethernet, Power over Ethernet (PoE), CATx and other demanding structured cabling applications including HDBaseT applications.
This cable is 3rd party tested and complies with a wide range of electrical and safety standards including ISO/IEC11801, CENELEC EN50173-1:2011, and ANSI/TIA-568-C2 making it appropriate for almost every indoor application.
This cable comfortably exceeds the CAT6 requirements for insertion loss, crosstalk, and return loss.
The cable is tested as a full channel solution and is especially compatible with the range of shielded GigaTrue® jacks, Patch cables, and patch panels.
Environmental — RoHS / RoHS2 Compliant
CE — LVD (2006/95/EC) , RoHS2(2011/65/EC)
Construction — 23 AWG Solid Bare Copper Twisted-Pair Conductors, Polyethylene Insulation, PE X-Filler, F/UTP Overall Foil Screen with Drain Wire, LSZH Jacket
Applicable Standards
Electrical —
2.2 edition ISO/IEC 11801, Cat.6;
CENELEC EN 50173-1:2011, Cat.6;
ANSI/TIA-568-C.2, Cat.6;
2nd edition IEC61156-5, Cat.6-Level 2, Type 2, Grade 2;
CENELEC EN 50288-6-1
Safety —
CENELEC EN 60332-1-2 / IEC 60332-1-2;
CENELEC EN 50268-1 / IEC 61034-1;
CENELEC EN 50268-2 / IEC 61034-2, inc1. Amendment 1;
CENELEC EN 50267-2-3 / IEC 60754-2
Materials/Construction —
CENELEC EN 60811-1-1, clause 9.2 / IEC 60811-1-1, clause 9.2.7;
CENELEC EN 60811-1-3, clause 10 / IEC 60811-1-3, clause 10;
CENELEC EN 60811-3-1, clause 9.2 / IEC 60811-3-1, clause 9.2;
CENELEC EN 60811-1-2, clause 8.1 / IEC 60811-1-2, clause 8.1;
CENELEC EN 50290-2-27, CENELEC EN 50290-2-23
Physical
Conductors —
Material: 23AWG Solid Bare Copper;
Diameter: 0.550 ± 0.02 mm
Insulation —
Material: HDPE;
Diameter: 1.08 ± 0.02mm
Shielding —
Filler: PE Filler (0.7 x 5.6mm);
Mylar Tape PET (25 x 0.025mm);
Drain Wire Solid Tinned Copper (1/0.48mm);
Al-Mylar Tape Laminated Aluminum-Polyester (23 x 0.063mm)
Jacket —
Material: LSZH;
Diameter: 7.2 ± 0.2mm;
Colour: Grey, Blue, Green, Red, Yellow, Purple
Packaging — Wooden Spool
Temperature —
Installation: -20°C up to +60°C;
Operation: 0°C up to +60°C
Min Bend Radius —
Installation: 6 x overall diameter;
Operation: 4 x overall diameter;
Max Pulling Tension — 90 N
Flame Retardance — IEC 60332-1-2
Electrical Characteristics at 20°C
Characteristic Impedance at 100 MHz — 100 ± 15 Ohm
Maximum Conductor DC Resistance — 93.8 Ohm/km
Mutual Capacitance — 56 nF/km
Maximum Capacitance — 330pF/100m (Unbalanced Pair to Ground)
Maximum Propagation Delay — 536 ns/100m
Maximum Delay Skew — 40 nS/100m
Max. Operating Voltage — 300 V rms