AC Leakage Current Throughout Overall Jacket — AC 1500V < 10 mA ACR (Minimum at 100-m) — 13.3 dB at 100 MHz Attenuation (Minimum at 100-m) — 22.0 dB at 100 MHz; 32.4 dB at 200 MHz; 44.9 dB at 350 MHz Cable Type — 4-pair UTP, 300 V Capacitance Unbalance (Maximum) — 330 pF/100-m (pair to ground) Capacitance, Mutual (Maximum) — 56 pF/km Characteristic Impedance — 1-350 MHz: 100 +/- 15 ohms Cold Bend Test — -20°C at 4 hours; no crack Conductor — 24 AWG, solid, bare copper Conductor Resistance (Maximum) — 93.8 ohm/67°F Dielectric Strength — AC: 1.5 KV/2 sec DC Resistance Unbalance (Maximum) — 5% Delay Skew (Maximum) — 1-350 MHz: 40 nS/100-m EL-FEXT (Minimum at 100-m) — 23.8 dB at 100 MHz; 17.7 dB at 200 MHz; 12.9 dB at 350 MHz Input Impedance — 1-100 MHz: 100 +/- 15 ohms Insulation Material — HDPE; Thickness Average and minimum: 0.007inch; Diamter: .035 +/- 0.0007inch Insualtion Shrinkback — 150 m/m; 121°C at 1hr. at 9.5 m/m Jacket — 0.188inch OD NEXT (Minimum at 100-m) — 35.3 dB at 100 MHz; 30.8 dB at 200 MHz; 27.1 dB at 350 MHz Outside Diamater — PVC: 0.18inch +/- 0.007inch Propagation Delay — 536 nS/100-m at 350 MHz PS-ACR (Minimum at 100-m) — PVC: 10.3 dB at 100 MHz PS-ELFEXT (Minimum at 100-m) — 20.8 dB at 100 MHz; 14.7 dB at 200 MHz; 9.9 dB at 350 MHz PS-NEXT (Minimum at 100-m) — 32.3 dB at 100 MHz; 27.8 dB at 200 MHz; 24.1 dB at 350 MHz Rating Temperature Voltage — 75°C; 300V Return Loss — 20.1 dB at 100 MHz Spark Test — 2.5 KV Velocity Of Propagation (Minimum) — 62.1% at 350 MHz Weight — 9.5 kg/304.8-m